Zum Inhalt springen

WSAL23626 – RS232 – 485 – 422 TO ETH (B)/en

Aus JW Tech Wiki
Version vom 30. August 2026, 00:32 Uhr von JWTechPublisher (Diskussion | Beiträge) (Freigegebenes Produktbild und Katalogposition ergänzt)
(Unterschied) ← Nächstältere Version | Aktuelle Version (Unterschied) | Nächstjüngere Version → (Unterschied)

Documentation notice: This technical documentation was independently rewritten from an archived supplier source. Check technical details and commands against the product version and manufacturer documentation before use.

Product view Rail-Mount Serial Server, RS232/485/422 to RJ45 Ethernet Module, TCP/IP to serial, POE Function Optional
Rail-Mount Serial Server, RS232/485/422 to RJ45 Ethernet Module, TCP/IP to serial, POE Function Optional

Catalog location in the JW Tech Shop:

  • WSAL23626 – Rail-Mount Serial Server, RS232/485/422 to RJ45 Ethernet Module, TCP/IP to serial, POE Function Optional: IoT / Communication → Wired Comm / Converter → Ethernet TO UART / RS232 / RS485
  • WSAL24759 – Rail-Mount Serial Server, RS232/485/422 to RJ45 Ethernet Module, TCP/IP to serial, POE Function Optional: Other products

Summary

A rail-mount serial server that converts RS232/485/422 serial signals to TCP/IP via an RJ45 Ethernet module with optional PoE power. It functions as an IoT gateway and Modbus gateway for industrial data acquisition.

Related products at JW Tech

Technical overview

  • Interfaces: 1 isolated RS232/485/422 port, 1 10/100 Mbit/s RJ45 Ethernet port with 2 kV surge protection; PoE (IEEE 802.3af) is only available on models labeled “POE”
  • Power: screw terminals accepting DC 6–36 V or PoE through the network port; barrel connector outer diameter 5.5 mm, inner diameter 2.1 mm
  • Serial parameters: baud rates 300–115200 bps, 5–9 data bits, parity none/odd/even/mark/space, no flow control
  • Operating modes: TCP server (up to 30 concurrent connections), TCP client (up to 7 destination IPs), UDP, and UDP multicast; TCP client also supports a coexisting TCP server function
  • Protocols: ETHERNET, IP, TCP, UDP, HTTP, ARP, ICMP, DHCP, DNS; configuration via PC software, web browser, or device-management library
  • Advanced features: Modbus RTU-to-TCP gateway (storage and non-storage modes), MQTT gateway, JSON-to-Modbus RTU/645 meter protocol, NTP time sync, custom heartbeat/registration packets, password authentication for TCP connections
  • Dimensions: 88.7 × 64.5 × 24.2 mm; operating temperature −40 °C to 85 °C; humidity 5–95 % RH

Notes and version constraints

  • The IP addresses mentioned in the source (e.g., 192.168.1.200, ports 4196 and 1111) are example values from a test environment, not fixed defaults of the device.
  • The exact maximum current draw when powered directly at 24 V is not stated in the source; only a measurement at 12 V (0.96 A, 1.16 W) is given.
  • Firmware-specific configuration files (e.g., the 2043 web interface) must be re-downloaded depending on installed firmware; details depend on the specific firmware version.
  • RS485 wiring: short-distance links may work without 120 Ω termination resistors; multi-point long-distance buses should have 120 Ω resistors at both ends — exact placement must be verified on site.
  • If the web configuration page will not open because another firmware (MQTT, Jetson Modbus) overwrote the config files, manually re-downloading the correct web file is required.

Source and revision record