<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="de">
	<id>https://wiki.jw-tech.eu/index.php?action=history&amp;feed=atom&amp;title=WSAL24271_%E2%80%93_RS485-HUB-8P%2Fen</id>
	<title>WSAL24271 – RS485-HUB-8P/en - Versionsgeschichte</title>
	<link rel="self" type="application/atom+xml" href="https://wiki.jw-tech.eu/index.php?action=history&amp;feed=atom&amp;title=WSAL24271_%E2%80%93_RS485-HUB-8P%2Fen"/>
	<link rel="alternate" type="text/html" href="https://wiki.jw-tech.eu/index.php?title=WSAL24271_%E2%80%93_RS485-HUB-8P/en&amp;action=history"/>
	<updated>2026-10-23T21:52:04Z</updated>
	<subtitle>Versionsgeschichte dieser Seite in JW Tech Wiki</subtitle>
	<generator>MediaWiki 1.43.9</generator>
	<entry>
		<id>https://wiki.jw-tech.eu/index.php?title=WSAL24271_%E2%80%93_RS485-HUB-8P/en&amp;diff=2793&amp;oldid=prev</id>
		<title>JWTechPublisher: Freigegebene technische Dokumentation veröffentlicht; Text-only und noindex</title>
		<link rel="alternate" type="text/html" href="https://wiki.jw-tech.eu/index.php?title=WSAL24271_%E2%80%93_RS485-HUB-8P/en&amp;diff=2793&amp;oldid=prev"/>
		<updated>2026-09-06T07:56:27Z</updated>

		<summary type="html">&lt;p&gt;Freigegebene technische Dokumentation veröffentlicht; Text-only und noindex&lt;/p&gt;
&lt;p&gt;&lt;b&gt;Neue Seite&lt;/b&gt;&lt;/p&gt;&lt;div&gt;__NOINDEX__&lt;br /&gt;
&amp;#039;&amp;#039;&amp;#039;Documentation notice:&amp;#039;&amp;#039;&amp;#039; This technical documentation was independently rewritten from an archived supplier source. Check technical details and commands against the product version and manufacturer documentation before use.&lt;br /&gt;
&lt;br /&gt;
== Summary ==&lt;br /&gt;
The RS485-HUB-8P is an industrial-grade isolated RS485 hub with one master port and eight slave ports. It expands an RS485 bus into a star topology, provides hardware isolation against transients and interference, and can relay weakened signals over long runs. Power is supplied via screw terminals at DC 9–24 V.&lt;br /&gt;
&lt;br /&gt;
== Related products at JW Tech ==&lt;br /&gt;
* [https://shop.jw-tech.eu/p/WSAL24271 WSAL24271 – Industrial-grade Isolated 8-ch RS485 Hub, Rail-mount Support, Wide Baud rate Range]&lt;br /&gt;
&lt;br /&gt;
== Technical overview ==&lt;br /&gt;
* One master port (485A/485B) connects the device to the host; eight slave ports (OUT1A–OUT8A, OUT1B–OUT8B) each support up to 32 nodes.&lt;br /&gt;
* Baud rates are self-adaptive from 300 to 460800 bps; transmission media are standard parallel or twisted-pair cables.&lt;br /&gt;
* Communication is half-duplex over two wires (A/B); maximum range is 1200 m at 9600 bps, with shorter distances at higher rates.&lt;br /&gt;
* Hardware isolation protects the RS485 line from lightning strikes, high voltage, strong current, and interference; the hub acts as a transparent signal repeater without its own protocol logic.&lt;br /&gt;
* For runs exceeding 1200 m, the hub can be used as a relay to compensate for signal attenuation and extend communication distance.&lt;br /&gt;
* Power supply: DC 9–24 V via screw terminals; at 12 V the no-load current is about 0.03 A (about 0.36 W).&lt;br /&gt;
* Operating temperature range: -45 °C to +85 °C, humidity below 95 % RH.&lt;br /&gt;
* When connecting multiple hubs to the same host interface, three prerequisites apply: consistent serial parameters, a half-duplex question-and-answer protocol such as Modbus RTU, and unique device addresses.&lt;br /&gt;
* Multiple hubs should not be connected in parallel to the host; use a handshake cascade connection, and avoid setting the scan cycle too short.&lt;br /&gt;
&lt;br /&gt;
== Notes and version constraints ==&lt;br /&gt;
* No specific command-line commands are documented; the device operates purely at the physical layer and functions as a transparent repeater without its own command language.&lt;br /&gt;
* The exact cascade wiring of multiple hubs is only described schematically in the document; the actual cabling should be verified by a technician.&lt;br /&gt;
* The power figure (12 V, 0.03 A / 0.36 W) comes from the FAQ and refers to no-load conditions; loaded behavior is not specified.&lt;br /&gt;
* The 32-node limit per port assumes all connected devices share identical serial parameters; mismatches may cause communication failures.&lt;br /&gt;
* The isolation protection guards against transients but does not replace external surge-protection devices for critical installations.&lt;br /&gt;
&lt;br /&gt;
== Source and revision record ==&lt;br /&gt;
* [https://www.waveshare.com/wiki/RS485-HUB-8P RS485-HUB-8P - Waveshare Wiki]&lt;br /&gt;
* Source revision: 98330&lt;br /&gt;
* Captured: 2026-09-04T04:05:38+00:00&lt;br /&gt;
* SHA-256: &amp;lt;code&amp;gt;5bbfa71726af398051474ab2eb4fdec435079c4b4f8511593b8c65e3ecb4f195&amp;lt;/code&amp;gt;&lt;/div&gt;</summary>